Electrical data
| Operating voltage [V] |
18…30 DC |
| Current consumption [mA] |
100…700; (US) |
| Protection class |
III |
Sensor supply US
| Current rating per port [A] |
0.1 |
Inputs / outputs
| Number of inputs and outputs |
Number of digital inputs: 12 |
Inputs
| Number of digital inputs |
12; (6 x 2 PNP type 2 according to IEC 61131-2) |
| Sensor supply of the inputs |
IO-Link |
| Power supply [V] |
16…30 |
Interfaces
| Communication interface |
IO-Link |
| SDCI standard |
IEC 61131-9 |
| Transmission type |
COM2 (38,4 kBaud) |
| IO-Link revision |
1.1 |
| SIO mode |
no |
| Required master port type |
A |
| Min. process cycle time [ms] |
4.3 |
| Supported DeviceIDs |
| Type of operation |
DeviceID |
| Default |
995 |
|
Operating conditions
| Ambient temperature [°C] |
-25…60 |
| Storage temperature [°C] |
-25…70 |
| Max. relative air humidity [%] |
75; (5…75) |
| Max. height above sea level [m] |
2000 |
| Protection |
IP 65; IP 67; IP 69K; (operation with stainless steel protective caps: IP 69K) |
| Protection rating (NEMA 250) |
6P |
| Pollution degree |
2 |
| Chemical media |
| ISO 16750-5 |
HLP, CC, DB, DC, DD, CA |
| NEMA 250 5.13.1 |
AA |
|
Tests / approvals
| EMC |
| EN 61000-6-2 |
|
| EN 61000-6-3 |
|
| IEC 61131-9 |
|
|
| Shock resistance |
|
| Vibration resistance |
| DIN EN 60068-2-64 |
|
| DIN EN 60068-2-6 |
|
|
| MTTF [years] |
197 |
Mechanical data
| Weight [g] |
300 |
| Materials |
housing: PA grey; socket: stainless steel (1.4404 / 316L) |
| Sealing material |
EPDM |
Displays / operating elements
| Display |
| operation |
1 x LED, green |
| fault |
1 x LED, red |
| function |
1 x LED, yellow |
|
Accessories
| Accessories (optional) |
| protective cap for M12 sockets |
|
Electrical connection – IO-Link
| X1 |
Connector: 1 x M12; coding: A |
Electrical connection – Inputs
| X1.0…X1.5 |
Connector: 6 x M12; coding: A; Sealing: EPDM |
Reviews