Application
| Application |
field installation |
Electrical data
| Operating voltage [V] |
26.5…31.6 DC |
| Max. current consumption from AS-i [mA] |
250 |
| Max. current load total [A] |
4 |
| Additional voltage supply [V] |
10…30 DC; (AUX) |
| Max. current consumption from additional supply [mA] |
4000; (AUX) |
| Integrated watchdog |
yes |
Inputs / outputs
| Number of inputs and outputs |
Number of digital inputs: 4; Number of digital outputs: 4 |
Inputs
| Number of digital inputs |
4 |
| Input circuit of digital inputs |
PNP; (type 2 according to IEC 61131-2) |
| Sensor supply of the inputs |
AS-i |
| Power supply [V] |
20…30; (DC) |
| Max. total current rating of inputs [mA] |
200 |
| Input current limitation [mA] |
15 |
| Input current High [mA] |
6…10 |
| Input current Low [mA] |
0…2 |
| Switching level high [V] |
> 11 |
| Digital inputs protected against short circuits |
yes |
Outputs
| Number of digital outputs |
4 |
| Circuit |
PNP |
| Voltage range DC [V] |
10…30; (AUX) |
| Max. current load per output [mA] |
2000; (utilisation category DC-13 (control of electromagnets): 20 W (IEC 60947-5-1)) |
| Max. current load outputs total [A] |
4 |
| Short-circuit proof |
yes |
| Electrically separated |
yes |
| Actuator supply outputs |
AUX |
Operating conditions
| Ambient temperature [°C] |
-25…80 |
| Storage temperature [°C] |
-25…80 |
| Max. relative air humidity [%] |
90; (non condensing) |
| Max. height above sea level [m] |
2000 |
| Protection |
IP 67; (when flat cables are used E7400x / E7401x) |
Tests / approvals
| EMC |
| EN 61000-6-2 |
|
| EN 62026-2 |
|
| EN 50581 |
|
|
| MTTF [years] |
193 |
| UL approval |
|
AS-i classification
| AS-i version |
2.11; 3.0 |
| AS-i addressing |
IR addressing possible |
| Extended addressing mode |
no |
| AS-i profile |
S-7.0.E |
| AS-i I/O configuration [hex] |
7 |
| AS-i ID code [hex] |
0.E |
| AS-i certificate |
46001 |
| Assignment of the data bits |
| data bit |
D0 |
D1 |
D2 |
D3 |
| input |
1 |
2 |
3 |
4 |
| socket |
I-1 |
I-2 |
I-3 |
I-4 |
| pin |
2+4 |
2+4 |
2+4 |
2+4 |
| Output |
1 |
2 |
3 |
4 |
| socket |
O-1 |
O-2 |
O-3 |
O-4 |
| pin |
4 |
4 |
4 |
4 |
|
Mechanical data
| Weight [g] |
386 |
| Materials |
PA; socket: brass nickel-plated; O-ring: FKM |
Displays / operating elements
| Display |
| switching status |
LED, yellow I1…I4, O1…O4 |
| operation |
LED, green AS-i, AUX |
| errors |
LED, red |
|
Accessories
| Accessories (optional) |
| Stainless steel sleeve, for installation in case of high mechanical stress , E70402 |
|
Remarks
| Remarks |
| Do not connect any of the following points to an external potential: |
| I-, I+, I1, I2, I3, I4 |
| The connections are electrically connected with the AS-i cable. |
|
| Pack quantity |
1 pcs. |
Electrical connection – AS-i
|
Connector: M12; coding: A |
Electrical connection – Inputs
|
Connector: M12; coding: A |
Electrical connection – Outputs
|
Connector: M12; coding: A |
Reviews