Application
| Application |
I/O modules for field applications |
| Daisy-chain function |
power supply; fieldbus interface |
Electrical data
| Operating voltage [V] |
19…31.2 DC; (US) |
| Protection class |
III |
| Additional voltage supply [V] |
19…31.2 DC; (UA) |
Actuator supply UA
| Current rating per port [A] |
1.6 |
Sensor supply US
| Current rating per port [A] |
0.2 |
Inputs / outputs
| Total number of inputs and outputs |
12; (configurable) |
| Number of inputs and outputs |
Number of digital inputs: 12; Number of digital outputs: 8 |
Inputs
| Number of digital inputs |
12; (IO-Link Port Class A: 4 x 2; IO-Link Port Class B: 4 x 1) |
| Switching level high [V] |
15…30 |
| Switching level low [V] |
-3…5 |
| Digital inputs protected against short circuits |
yes |
Outputs
| Number of digital outputs |
8; (IO-Link Port Class A: 4 x 1; IO-Link Port Class B: 4 x 1) |
| Max. current load per output [mA] |
200 |
| Short-circuit proof |
yes |
| Actuator supply outputs |
24 V DC |
Interfaces
| Communication interface |
IO-Link; PROFIBUS |
IO-Link Master
| Transmission type |
COM1 (4,8 kBaud); COM2 (38,4 kBaud); COM3 (230,4 kBaud) |
| IO-Link revision |
1.1 |
| Number of ports class A |
4 |
| Number of ports class B |
4 |
Operating conditions
| Ambient temperature [°C] |
-25…60 |
| Storage temperature [°C] |
-25…85 |
| Max. relative air humidity [%] |
95 |
| Protection |
IP 65; IP 67 |
Tests / approvals
| EMC |
| EN 61000-6-2 |
|
| EN 61000-4-2 ESD |
6 kV contact discharge / 8 kV air discharge |
| EN 61000-4-3 |
|
| EN 61000-4-4 |
|
| EN 61000-4-5 |
|
| EN 61000-4-6 |
|
|
| Shock resistance |
|
| Vibration resistance |
|
Mechanical data
| Weight [g] |
577 |
| Materials |
housing: PA; socket: brass nickel-plated |
| Sealing material |
FKM |
Remarks
| Remarks |
| For further information please see the operating instructions. |
|
| Pack quantity |
1 pcs. |
Electrical connection – PROFIBUS IN
| X21 |
Connector: M12; coding: B |
Electrical connection – PROFIBUS OUT
| X22 |
Connector: M12; coding: B; Sealing: FKM |
Electrical connection – Process connection
| IO-Link Port Class A X01…X04 |
Connector: M12; coding: A; Sealing: FKM |
Electrical connection – power supply IN
| X31 |
Connector: M12; coding: T |
Electrical connection – power supply OUT
| X32 |
Connector: M12; coding: T; Sealing: FKM |